complete and show the location, size, dimensions, part identification, and
other information. Additional sheets may be added. The as-built drawings
shall be jointly inspected for accuracy and completeness by the
Contractor's quality control representative and by the Contracting Officer
prior to the submission of each monthly pay estimate. Upon completion of
the work, the Contractor shall submit three full sized sets of the marked
prints to the Contracting Officer for approval. If upon review, the
as-built drawings are found to contain errors and/or omissions, they will
be returned to the Contractor for correction. The Contractor shall correct
and return the as-built drawings to the Contracting Officer for approval
within ten calendar days from the time the drawings are returned to the
Contractor.
PART 2
PRODUCTS
Products shall conform to the following requirements. Items of the same
classification shall be identical including equipment, assemblies, parts,
and components. Products for aerial construction shall conform to IEEE C2
for [heavy] [medium] [light] loading districts, Grade B construction.
2.1
STANDARD PRODUCT
Material and equipment shall be the standard product of a manufacturer
regularly engaged in the manufacture of the product and shall essentially
duplicate items that have been in satisfactory use for at least 2 years
prior to bid opening.
2.2
NAMEPLATES
2.2.1
General
Each major component of this specification shall have the manufacturer's
name, address, type or style, model or serial number, and catalog number on
a nameplate securely attached to the equipment. Nameplates shall be made
of noncorrosive metal. As a minimum, nameplates shall be provided for
switchgear, and grounding resistors.
2.2.2
Liquid-Filled Transformer Nameplates
**************************************************************************
NOTE: Coordinate Nameplate C information with the
manufacturer. Select 50 ppm for Army projects and 2
ppm for Air Force projects.
**************************************************************************
accordance with IEEE C57.12.00. Nameplates shall indicate the number of
gallons and composition of liquid-dielectric, and shall be permanently
marked with a statement that the transformer dielectric to be supplied is
non-polychlorinated biphenyl. If transformer nameplate is not so marked,
the Contractor shall furnish manufacturer's certification for each
transformer that the dielectric is non-PCB classified, with less than [50]
[2] ppm PCB content in accordance with paragraph MISCELLANEOUS Liquid
Dielectrics. Certifications shall be related to serial numbers on
transformer nameplates. Transformer dielectric exceeding the [50] [2] ppm
PCB content or transformers without certification will be considered as PCB
insulated and will not be accepted.
SECTION 16311A