verify adherence to the procedures specified in this section.
l.
Design/Construction deficiencies: Within 3 working days after the
TAB Agency has encountered any design or construction
deficiencies, the TAB Supervisor shall submit written notification
directly to the Contracting Officer, with a separate copy to the
Contractor, of all such deficiencies. Provide in this submittal a
complete explanation, including supporting documentation,
detailing deficiencies. Where deficiencies are encountered that
are believed to adversely impact successful completion of TAB, the
TAB Agency shall issue notice and request direction in the
notification submittal.
m.
TAB Field Check: The TAB team supervisor shall attend and
supervise [Season 1] [and Season 2] TAB field check.
1.8.3.4
TAB Team Field Leader
a.
Field manager: Manage, in the field, the accomplishment of the
work specified in Part 3, "Execution."
b.
Full time: Be present at the contract site when [DALT field work
or ]TAB field work is being performed by the TAB team; ensure
day-to-day TAB team work accomplishments are in compliance with
this section.
c.
Prerequisite HVAC work: Do not bring the TAB team to the contract
site until a copy of the prerequisite HVAC Checklist, with all
work items certified by the Contractor to be working as designed,
reaches the office of the TAB Agency.
1.8.4
Test Reports
[1.8.4.1
Data from DALT Field Work
Report the data for the Pre-final DALT Report and Certified Final DALT
Report in compliance the following requirements:
a.
Summary Report Forms as shown on Page 6-2 of SMACNA Leakage Test
Mnl. In addition, submit in the report, a marked duct shop
drawing which identifies each section of duct tested with assigned
node numbers for each section. Node numbers shall be included in
the completed report forms to identify each duct section. The
report shall be reviewed and certified by the TAB supervisor.
b.
The TAB supervisor shall include a copy of all calculations
prepared in determining the duct surface area of each duct test
section. In addition, the DALT reports shall contain copy(s) of
the calibration curve for each of the DALT test orifices used for
testing.
c.
Instruments: List the types of instruments actually used to
measure the data. Include in the listing each instrument's unique
identification number, calibration date, and calibration
expiration date. Instruments shall have been calibrated within
one year of the date of use in the field. Instrument calibration
shall be traceable to the measuring standards of the National
Institute of Standards and Technology.
SECTION 15950N