1.8
ENVIRONMENTAL REQUIREMENTS
1.8.1
Air Permits
Permits for construction and operation of the boiler plant shall be
obtained from the local environmental regulatory agency prior to the start
of construction.
1.8.2
Boiler Emissions
Comply with local, state, and federal emission regulations for the fuel to
be fired.
1.8.3
Oil Burner/Windbox Package
The emission requirements shall be met at the maximum required continuous
output. The burner shall meet environmental rules and regulations.
Emission requirements to be considered are oxides of nitrogen (NOx),
opacity, particulates, sulfur dioxide, and carbon monoxide. Compliance with
NOx emission regulations shall be met using one [a combination] of the
following:
a.
Low NOx burners
b.
Flue gas recirculation
c.
Other NOx reduction methods
1.9
EXTRA MATERIALS
a.
Furnish two extra sets of air filters for each compressor.
**************************************************************************
NOTE: At the text below, choose one of the two
following items in coordination with the option
chosen in Part 2 "Compressed Air Dessicant Air
Dryer" or "Compressed Air Refrigerated Air Dryer."
**************************************************************************
[b.
Furnish 4 spare prefilters and 4 spare afterfilters for
[c.
Furnish 4 spare disposable cartridge type prefilters and
d.
Furnish a spare set of refractory bricks for each thawing unit.
PART 2
PRODUCTS
2.1
MATERIALS
Provide materials free of defects which would adversely affect the
assembly. Materials not specified herein shall be of the same quality used
for the intended purpose in commercial practice. Unless otherwise
specified herein, equipment, material, and articles incorporated in the
work covered by this specification shall be new.
SECTION 15502N